打印本文 关闭窗口 | |
电力变压器绕组轴向振动稳定性分析来源于瑞达科技网 | |
作者:佚名 文章来源:网络 点击数 更新时间:2011/1/25 文章录入:瑞达 责任编辑:瑞达科技 | |
|
|
关键词:电力变压器;机电耦合振动;稳定性; 绕组变形 1 Introduction A power transformer has to be designed and built to withstand thermal and mechanical stresses resultingfrom all external short circuits during its normal life, which may be expected to exceed 20 years. An extensive program of transformer short circuit testing and analysis has been carried out to define failure modes and determine the limits of design parameters [1,2]. The windings of transformer may be destroyed by various causes, such as collapse of the conductors, failure in the insulation and erosion of the conductor insulation caused by rubbing, which lead to electrical breakdown. So it is essential for the designer to estimate the stability, displacements and forces of the windings during short circuit conditions. where,
The model-transformer leakage magnetic field is solved by a formulation in terms of magnetic vector potential A. The magnetic induction intensity B is given by Curl A. The govern equation of the transformer leakage magnetic field is as follows [4]: current density in the winding. u1 and u2 are axial displacements of windings. It is shown from this solution that the magnetic vector potential A is a function of winding currents and displacements (u1 and u2). and Q is generalized force of the system, q is generalized coordinate of the system. T, pm and pe are the kinetic energy, elastic energy and magnetic energy of the system, respectively. To the electromechanical coupled vibration of transformer windings, we haveKinetic energy of the system: where It can be seen, from equation (10) and (11), that the relation between magnetic forces and the winding displacements (u1 and u2) is nonlinear. If the displacement of transformer winding is small enough, it is possible to approximate this nonlinear relation to a linear function. These linealy approximate magnetic forces are where, At the static equilibrium point of the transformer’s windings, the magnetic forces f10 and f20 are equal to zero. For the model transformer, Fig. 2 shows that their values are almost equal to zero. Equation (9), (1) and (2) are nonlinear electromechanical coupled vibration equations for the transformer windings. Equation (14), (1) and (2) are the simplified forms. In this paper, these simplified equations are used to assess vibration stability of the transformer’s windings. When the ampere-turn distributions in inner and outer windings are unbalanced (such as the unbalance caused by winding displacement along axial), the windings repulse each other. The axial magnetic force between inner and outer windings is a function of winding’s relative displacements d = u1 - u2. It can be obtained by an analytical solution (Eq.(10) and Eq.(11)). The currents through the winding are given by Eq.(1). The magnetic forces in axial direction are shown in Fig.2. It is shown that the magnetic forces increase with the increasing of winding’s relative distance d. When d/H<<1 (H is the height of transformer winding), the relationship between magnetic force and the winding’s relative displacement is nearly linear. We can get the magnetic stiffness ke of the transformer’s windings from Fig.2. They are Mathieu’s differential equation group without damping. Because of the complexity of Eq.(16), there is no analytical solution obtained. As a general transformer windings' vibration problem, it is indispensable to solve Eq.(16) by numerical method. To the model transformer, we have Lets d=u1-u2 , it’s the relative displacement of two windings. Considering of Eq.(17), the following vibration equation is obtained from equations (16). The well known solution of the Mathieu equation (e.g. reference [6]) is presented here in the form of Strutt diagram in figure 3. The stability and instability regions are shown in the Strutt diagram. For the vibration system with damping, the stable region expands [6].
Examining the definitions of d and e in equation (20), one can see that l and I0 are important parameters influencing d and e. The parameter I0 appears in the expressions for both d and e. With the increasing of I0 , e increases and d decreases. Thus, it can be concluded that the possibility of instability is greater at high current I0. This means that the high currents through the transformer windings may cause instability of the winding’s vibration. Parameter l influences d only, and the increase of l leads to increase of d, but without any changes in e. Therefore, increasing l may be useful to stabilize axial vibration of transformer windings. This means that increasing the stiffness of the supporting structure of the windings is useful to the stability of the axial vibration of transformer windings. The constant le is another parameter which alters the magnitude of d and e , as discussed previously, which fully depends on the configuration of the transformer windings. Reference[1] Wang Z Q, Shi C L, Peng Z Z. The axial dynamic response of large power transformer windings under short circuit conditions by FEM [C]. New Advances in Model Syntheses of Large Structure. Edited by L.Jezequel, 1997.
|
|
打印本文 关闭窗口 |